Section 4 Auto-Zone Plus
4-22 Start-Up and Troubleshooting
1.3.12 Troubleshooting Checklist
No Zones are Communicating
Is the CommLink IV connected and plugged in?
Are the Zone Manager addresses set to 17?
In an Auto-Zone Plus system all Zone Managers are set to Address = 17.
Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.
Is the Comm Loop open or shorted?
Are the Zone Controller address switches set correctly? See the addressing chart.
Are the Zone Controllers powered? Check 24 VAC to the controllers.
Is the Network Loop shorted to or connected to any of the Local loops? Check
Network Loop voltages.
Is the System Manager connected to a Local loop?
Do not connect the system manager to the network loop!
Some Zones are communicating but others are not:
Is the Zone Manager set for the correct number of zones?
Are the Zone Controller address switches set correctly? See the addressing chart.
Are the Zone Controllers powered? Check 24 VAC to the controllers.
Is the REC LED on the missing Zone Controller “flickering”? See Zone Controller
introduction for location of the REC LED.
Is the SCAN LED blinking an error code? See the Blink Code chart.
Are Comm Loop voltages correct at the missing unit? See the Comm Loop
troubleshooting guide.