Auto-zone-control-systems CommLink 5 Technical Guide, Installation Instructi Manual de usuario Pagina 7

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 6
CommLink 5 Technical Guide
7
Operator Interface
Baud Rate Setting
Setting the CommLink 5 Baud Rate
CommLink 5 Baud Rate Setting
The Baud Rate Switch Located On The Back Of
The CommLink 5 Housing Must Be Set Correctly
For Your Specific Application In Order For The
CommLink 5 To Function At Maximum Efficiency.
The Should Be Set To “High” In The
Following Situations:
You Are Using Only 2 Controllers, Only
GPC-XP Controllers, or Only VCB-X
Controllers On Your System.
The CommLink 5 Is Factory Set For Low Baud
Rate Applications.
Baud Rate
The Baud Rate Should Be Set To “Low” In The
Following Situations:
You Are Using Orion Controllers Or Are
Using Orion Controllers In Combination
With VCB-X or GPC-XP Controllers. For
Example, VCB-X or GPC-XP Controllers
With VCM-X or VCM Controllers.
AZ
MULTIPLE
HIGH
SINGLE
LOW
BAUDLOOP
R (+)
24V
GND
SHLD
T(-)
SERIAL #
Switch Set To High Baud
Rate (115,200)
Back of CommLink 5
HIGH
LOW
BAUD
Switch Set To Low Baud
Rate (Anything Less Than
115,200)
HIGH
LOW
BAUD
Figure 3: Setting the Baud Rate
Revised: 11/05/12
Vista de pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 15 16

Comentarios a estos manuales

Sin comentarios