EZ Zone/Auto-Zone
Upgrade 5
The basic steps required to upgrade your EZ
Zone system to an Auto-Zone system are:
z Determine what EZ Zone components
are currently installed on the system.
z Replace the existing EZ-Zone Master
Controller board with an Auto-Zone
Zone Manager controller board
z Replace the existing EZ Zone
EPROM’s in each Zone Controller
with a new Auto-Zone EPROM.
z Install return air and outside air
temperature sensors
EZ Zone to Auto-Zone upgrade allows you to
retain:
z All existing wiring
z Master Controller enclosure with
keypad and display
z Existing supply air and static pressure
sensors
z Existing bypass damper
z All Zone Dampers
z * All Zone Controllers
z Room sensors
z * Modem Link Central
z * All Master Interface Boards
z All Fan Terminal Controllers
EZ Zone Upgrade Overview
After upgrading your system from EZ Zone to
Auto-Zone, you will be able to take advantage
of many new enhancements including:
z
Damper actuators can be programmed
for direct or reverse operation
z Full modulating economizer control
capability including optional wetbulb
economizer control
z Outside air temperature sensor provides
lockout function for both heating and
cooling. When converted to Auto-Zone
Plus system only one outside air sensor
is required for the entire system
z Contact closure input for dirty filter
status
z Global and individual zone override
modes
z Zones can be set for voting or
nonvoting status
z Room sensor slide can be programmed
± 0° F to ± 5° F adjustment
from setpoint
z Staging delays, minimum off times,
and changeover intervals are
programmable
z Sensor offset calibration to correct
sensor errors due to poor location
z ZoneView enhanced graphical computer
front end software available when
CommLink and a PC are used
z System Manager operator interface
allows all controllers to be accessed from
one central location
* These controllers can be retained but they will re-
quire an EPROM chip upgrade to be compatible
with the Auto-Zone System.