Auto-Zone Systems 19
Zoning Design Guide
can cause air flow problems. These slide-in dampers
require that the damper frame be inside the duct. Imag-
ine an 8 x 10 rectangular duct using a slide in damper
with a frame thickness of 1”. The frame alone would
reduce the opening to 6 x 8.
Another possible problem encountered with rectangu-
lar dampers is the blade width. Many damper manufac-
turers supply dampers with 6” or 8” dampers blades.
This can become a major problem, for example, if the
Rectangular Dampers
Auto-Zone rectangular dampers are high quality alu-
minum construction with opposed/air foil designed
blades for superior control and have both blade and jamb
seals for tight shut off. The dampers are installed using
a mounting flange. The purpose for the flange mount-
ing is to allow as much unrestricted free space within
the duct as possible.
Many companies utilize slide-in type dampers which
Bypass & Slave Dampers Zone Dampers
Table 1-1: Round Damper Selection Data
Damper Round Duct Size
(Area Ft
2
)
6
(0.188)
8
(0.338)
10
(0.532)
12
(0.769)
14
(1.050)
16
(1.375)
CFM @ 1” Velocity Pressure
Air Flow Probe K Factor- For Pressure
Independent Applications Only
474 950 1417 2120 2908 3700
Velocity Through Zone Damper
FPM
Airflow Through Zone Damper - CFM
(P
S
inches W.C. With Air Damper Full Open)
750 - Zone
141
(0.03)
254
(0.02)
399
(0.01)
577
(0.02)
788
(0.01)
1031
(0.01)
1000 - Zone
188
(0.05)
338
(0.03)
532
(0.02)
769
(0.03)
1050
(0.02)
1375
(0.01)
1250 - Zone
235
(0.07)
423
(0.04)
665
(0.03)
961
(0.04)
1313
(0.03)
1718
(0.02)
1500 - Zone
282
(0.09)
507
(0.06)
798
(0.04)
1154
(0.05)
1575
0.04)
2062
(0.03)
1750 Bypass Only
329
(0.12)
592
(0.08)
931
(0.06)
1346
(0.06)
1838
(0.05)
2405
(0.04)
2000 Bypass Only
376
(0.15)
676
(0.10)
1064
(0.07)
1538
(0.07)
2100
(0.07)
2749
(0.05)
2250 Bypass Only
423
(0.18)
761
(0.13)
1197
(0.09)
1730
(0.09)
2363
(0.08)
3094
(0.06)
WattMaster reserves the right to change specifications without notice
1/2" Foil Faced
Insulation
Actuator
Round Damper
Blade Assembly
Control Enclosure
(Cover Removed)
A
IR
FLOW
AIRF
LO
W
Bypass & Slave Interface
1/2" Foil Faced
Insulation
Actuator
Zone Controller
Round Damper
Blade Assembly
Control Enclosure
(Cover Removed)
A
IR
F
L
O
W
A
I
R
F
L
O
W